Free Hot Water Pre-Engineered System Chart
Use the chart below to help calculate the number of panel's necessary for a commercial or residential system. Larger systems will need engineering and metering to select the proper system for the application.
Image |
Model |
Panels |
Series |
BTU's |
Sq. Ft. |
kWth |
GPD |
Storage |
| TSO150 |
1 |
4000 |
21,500 |
21.86 |
6.30 |
<70 |
40 |
| 01079-SC50 |
1 |
5000 |
23,100 |
22.28 |
6.75 |
<80 |
79 |
| 02079-SC40 |
2 |
4000 |
43,000 |
21.86 |
12.60 |
<120 |
79 |
| 02079-SC50,1,2 |
2 |
5000 |
46,200 |
22.28 |
13.50 |
<130 |
79 |
| 02105-SC70,1,2 |
2 |
7000 |
56,800 |
27.67 |
16.60 |
<150 |
105 |
| 03132-SC40 |
3 |
4000 |
64,500 |
21.86 |
18.90 |
121-170 |
132 |
| 03132-SC50,1,2 |
3 |
5000 |
69,300 |
22.28 |
20.25 |
131-185 |
132 |
| 03132-SC70,1,2 |
3 |
7000 |
85,200 |
27.67 |
24.90 |
150-225 |
132 |
| 06264-SC40 |
6 |
4000 |
129,000 |
21.86 |
37.80 |
171-330 |
264 |
| 06264-SC50,1,2 |
6 |
5000 |
138,600 |
22.28 |
40.50 |
186-345 |
264 |
| 06264-SC70,1,2 |
6 |
7000 |
170,400 |
27.67 |
49.80 |
226-425 |
264 |
| 09422-SC50,1,2 |
9 |
5000 |
207,900 |
22.28 |
60.75 |
346-505 |
2x 211 |
| 09422-Sc70,1,2 |
9 |
7000 |
255,600 |
27.67 |
74.70 |
426-615 |
2x 211 |
| 12528-SC50,1,2 |
12 |
5000 |
277,200 |
22.28 |
81.00 |
506-665 |
2x 264 |
| 12528-SC70,1,2 |
12 |
7000 |
340,800 |
27.67 |
99.60 |
616-800 |
2x 264 |
| SRCC Certified Solar Thermal Collectors |

|

|

|
FHW 7000 Series |
FHW 5000 Series |
FHW 4000 Series |
High Performance Thermal Collector
Intelligent Design
Deep Drawn Aluminum Tray
Highly Selective Absorbent Coating
2" Thermal Insulation 40/50 Rockwool
Tempered Low Iron Glass
Suitable for Closed Loop Systems
In Roof, Pitched and Flat Roof Installation
Dimensions - 81.6 X 48 X 3.6
Thermal Output –1.66 Kw per hour
Max Stagnation (f) 453 Max PSI-145
Absorber Capacity .43
Manifold 3/4 - Risers 3/8
Free Hot Water Item #: FHWC-FC-70275
Gross Area: 2.571 m2, 27.67 sf
Net Aperture: 2.34 m2, 25.14 sf
Weight - 108 Lbs
10 Year Limited Warranty
Approvals - SRCC OG 100
SRCC Daily BTU's - 28,400
|
High Performance Thermal Collector
Intelligent Design
Deep Drawn Aluminum Tray
Selective Absorbent Coating
Thermal Insulation Rockwool
Tempered Low Iron Glass
Suitable for Closed & Open Loop Systems
Pitched and Flat Roof Installation Systems
Dimensions - 79.5 X 40 X 3
Thermal Output –1.35 Kw per hour
Max Stagnation (f) 410 Max PSI-116
Absorber Capacity 1.1 gal.
Manifold 3/4 - Risers 3/8
Free Hot Water item #: FHWC-FC-50221
Gross Area: 2.070 m2, 22.28 sf
Net Aperture: 1.85 m2, 19.91 sf
Weight - 84 Lbs
10 Year Limited Warranty
Approvals - SRCC OG 100
SRCC Daily BTU's - 23,100
|
High Performance Thermal Collector
Optimal Value for the Money
Aluminum Frame
PVD Selective Coating
Thermal Insulation - Polyurethane Foam
Tempered Solar Safety Glass
Suitable for Closed & Open Loop Systems
Pitched and Flat Roof Installation
Dimensions - 76.5 X 41 X 3
Thermal Output –1.26 Kw per hour
Max Stagnation (f) 453 Max PSI-145
Absorber Capacity .60 gal.
Manifold 3/4 - Risers 3/8
Free Hot Water item #: FHWC-FC-40220
Gross Area: 2.031 m2, 21.86 sf
Net Aperture: 1.89 m2, 20.30 sf
Weight - 60 Lbs
10 Year Limited Warranty
Approvals - SRCC OG 100
SRCC Daily BTU's - 21,500
|
Free Hot Water Analysis: |
(Number of gallons of hot water needed) * (8.34, the energy required to heat fluid 1 degree) * (Delta-T, the desired water temperature - the incoming water temperature) = (Daily Btu's required) / (SRCC collector daily Btu rating) = # of collectors |
5 units * 42 GPD = 210 * 8.34 * 65 = 113841/28,400 = 4 Collectors
Minimum Storage = 27.67 * 4 * 1.25 = 138.25 Gallons |
16 units * 42 GPD = 672 * 8.34 * 65 = 364291.2/28,400 = 12 Collectors
Minimum Storage = 27.67 * 12 = 332 Gallons |
52 units * 38 GPD = 1976 * 8.34 * 65 = 10224000/28,400 = 37.7 Collectors
Minimum Storage = 27.67 * 38 = 1051 Gallons |
FHW offers complete installation documentation and support.
Solar Hot Water Systems should be purchased based on climate zone and hot water usage. For a free evaluation of a Solar Hot Water System for your residential or commercial application Contact Us.
|